What does the manufacturer distinguish?
Schneider Electric's application data distinguishes make, break and continuous current ratings and separates resistive and inductive load categories. Its continuous rating concerns carrying a load without opening or closing the circuit. A number copied without its rating function and conditions can therefore answer the wrong question.
Substation Drafting is independent and is not affiliated with Schneider Electric. Use the selected device's exact current data. Do not transfer an AC rating to a station DC circuit, or a contact rating to the relay coil.
Sources: Schneider Electric: Schneider Electric 8501CT9601 Industrial Control Relays: Application Data
Which fields should the schematic reference retain?
Identify the actual output contact and its assigned circuit. A general description such as relay rated 5 A leaves the function, voltage and duty unclear. Keep manufacturer conditions linked to the approved circuit assessment rather than reconstructing them from a product summary.
| Rating field | Controlled reference | Mismatch to flag |
|---|---|---|
| Device and contact | Exact variant, contact and circuit tag | A different output used |
| Function | Make, break or continuous carry | One function substituted for another |
| Electrical basis | AC or DC and applicable voltage | AC value copied into DC duty |
| Load category | Actual manufacturer classification | Resistive value used for other duty |
| Duty conditions | Relevant duration, operations and restrictions | Maximum treated as a complete assessment |
| Disposition | Responsible engineer and revision | Unsupported suitability shown as approved |
What does a carrying-rating mismatch look like?
Illustrative example. A fictional contact schedule lists 5 A continuous carry, but its invented permitted break rating for the specified DC duty is 0.5 A. The circuit review shows 1 A for that same break condition. Comparing only 1 A with 5 A misses the separate 0.5 A reference.
The drafter flags the incomplete assessment and retains the source references for engineering review. These numbers are not specifications for a real relay, a universal derating ratio or authority to operate the circuit. A match on steady current alone does not resolve every make, break or duty requirement.
How should a substitution be coordinated?
Reconcile the output variant, contact duty, circuit reference and approved device schedule before issuing a revised schematic. Keep coil-voltage checks separate even when the replacement has the same nominal coil value. An unchanged terminal layout does not prove identical contact capability.
Do not prescribe series contacts, suppression components or wiring changes from this worksheet. Engineering sign-off is performed only by the registered engineer on the job; no live testing or switching instruction is provided.
Common questions
What else should the bid team know?
Does a continuous ampere rating establish break capability?
No. Check the correct function and conditions.
Can an AC contact rating be used as a DC rating?
Do not assume it. Obtain the selected device's actual data and engineering assessment.
Is the contact rating the coil-voltage range?
No. They concern separate functions.