Which relay definition applies to the drawing?
OMRON's relay classification guide distinguishes single-stable and latching relays. In its single-stable example, the relaxed state connects the moving contact to NC and leaves NO disconnected; energizing the coil changes those contacts. A latching relay can retain its set state after coil current is removed.
That distinction matters when a drawing states de-energized or normal. Confirm the actual selected relay type and reference state; do not apply a single-stable convention to every device. Substation Drafting is independent and is not affiliated with OMRON.
Sources: OMRON: General relay classifications and operating states
What should a contact-to-alarm drawing trace retain?
Use the approved model documentation, schematic and input or alarm logic schedule together. A contact label and a software alarm name are evidence about different parts of the chain.
| Trace field | Source to retain | Drawing check |
|---|---|---|
| Device | Selected model and relay type | Single-stable, latching or another defined device |
| Reference condition | Explicit state described by the drawing | Avoid an undefined normal condition |
| Terminals | Actual common, NO and NC identifiers | No inferred terminal numbering |
| Circuit | Controlled wire and terminal references | Follow the selected contact to its destination |
| Input interpretation | Approved receiving input or logic schedule | Record how contact state is interpreted |
| Alarm meaning | Approved alarm definition | Do not derive meaning from NC alone |
| Disposition | Design owner and resolved query | Affected drawings and schedules agree |
How can contact state and alarm meaning be confused?
Illustrative example. A fictional approved single-stable relay drawing labels a contact NC. A separate approved alarm schedule defines what the receiving input means when that circuit is open or closed. A draft legend simply calls NC alarm active without referencing the alarm schedule.
The reviewer flags that unsupported mapping and asks the design owner to confirm the intended logic. This example specifies no real trip function, live state, terminal numbers or safe operating condition. An NC label cannot by itself establish that a real alarm is active or inactive.
If the device is replaced by a different type, reopen the reference-state and terminal checks. Similar symbols or mounting arrangements do not establish identical behaviour.
What closes the drawing query?
Record the authorized device definition, drawing reference condition and approved alarm interpretation. Update the affected legend, schematic and schedule through the controlled drawing process, preserving the earlier issue and response.
This is a documentation consistency review. Do not energize a coil, test a live circuit, change wiring or alter protection logic to make a drawing agree. Engineering sign-off is performed only by the registered engineer on the job. The actual installed condition and safe work require authorized procedures and qualified personnel.
Common questions
What else should the bid team know?
Does NC always mean alarm active?
No. Apply the actual approved alarm interpretation.
Do all relays return when the coil is de-energized?
No. Confirm the selected device type; latching behaviour differs.
May a drafter alter logic to resolve the mismatch?
No. Obtain the authorized design disposition.