What does the dated manufacturer example show?
The cited SEL technical paper's Figure 9 shows input identifiers including IN102 alongside named signals in a particular generator breaker scheme. It is a dated example of device-specific naming, not a universal terminal map for every relay or a current project wiring instruction.
Substation Drafting is independent and is not affiliated with SEL. Obtain the actual relay hardware and firmware documentation and approved signal list. A protection function or familiar signal name alone cannot identify a physical pin.
What belongs in the mapping record?
Use one row per approved signal and distinguish the relay instance from its family name. Preserve drawing view and connector references so front and rear representations do not become accidental alternatives.
| Field | Controlled source | Review purpose |
|---|---|---|
| Relay instance | Approved panel equipment tag | Identify the correct installed instance |
| Device configuration | Model, hardware option and applicable revision | Avoid transferring a map between variants |
| Logical input | Approved relay signal name | Identify the intended logical point |
| Physical location | Connector and terminal reference | Locate the corresponding hardware input |
| External signal | Approved schematic and terminal schedule | Trace the correct source circuit |
| Review disposition | Responsible engineer's approved mapping | Preserve unresolved mismatches |
How can copying a familiar input label conceal a hardware mismatch?
Illustrative example. A fictional drawing revision retains logical input IN102 but the proposed replacement relay has a different approved hardware configuration. A drafter copies the previous physical terminal reference because the logical label looks familiar. The logical name has not verified the connector mapping.
The reviewer compares the two exact device documents and requests an approved mapping decision. The physical reference is revised only after that decision, with affected schematic and terminal rows reconciled. No real pin numbers or field wiring steps are supplied by this example.
What should the final review confirm?
Check the logical signal, hardware input location, source circuit and panel terminal reference as a continuous document trace. A mapped identifier does not prove polarity, voltage compatibility or approved protection logic. Those technical decisions need their own engineering evidence.
Retain the model and revision used for the mapping rather than a generic product brochure. Do not copy this dated paper into a live terminal schedule as a design. This article provides no energisation, testing or patching instruction. Engineering sign-off is performed only by the registered engineer on the job.
Common questions
What else should the bid team know?
Can an IN label be used as a terminal number?
No. Verify the actual device-specific physical map.
Does a matching signal name prove hardware compatibility?
No. Check model, options and approved engineering inputs.
Does the example authorise rewiring?
No. It illustrates a document trace only.
Primary sources
- Avoiding unwanted generator tripping, dated SEL technical paper, Figure 9Schweitzer Engineering Laboratories